Instruction REVISED 7/28/10 No. AERCO INTERNATIONAL, Inc., Northvale, New Jersey 07647 USA AC-106 MODBUS ® Communication Manual for ELECTRONIC
6 6. REFERENCE DOCUMENTS 1. Eurotherm 2000 Series Communications Handbook, # HA026230 2. Eurotherm 2404/2408 Control Setpoint Programmer Installa
78. ALARMS Table 4. Process Alarms DISPLAY MEANING _FSL* PV Full Scale Low Alarm. _FSH* PV Full Scale High Alarm. _dEu* PV Deviation Band Alarm _dHi
AC-106 INSTRUCTIONS - ECS COMMUNICATIONS 8Err4 Error 4: Keyboard failure. Stuck button or button was pressed during power-up Switch power off and th
THIS PAGE INTENTIONALLY BLANK ii
iii ELECTRONIC CONTROL SYSTEM COMMUNICATION INTERFACE TABLE OF CONTENTS Title Page 1. INTRODUCTION 1 2. COMMUNICATION BOARD 1 3. MODBUS COMMUNI
iv THIS PAGE INTENTIONALLY BLANK
AC-106 INSTRUCTIONS - ECS COMMUNICATIONS 1 ELECTRONIC CONTROL SYSTEM COMMUNICATION INTERFACE 1. INTRODUCTION The Electronic Control System (ECS), u
2Table 1. MODBUS Communication Signal Connections 2408 TEMPERATURE CONTROLLER COMPUTER CONTROL CABLE RS232/9-PIN RS232/25-PIN RS485 SIGNAL NAME PIN
3Table 2. Eurotherm Series 2400 Controller MODBUS Points MODBUS Data Address Menu Item Menu Item Description Units & Range Default/Comments
4 To change the modbus address: The address is defaulted to 1 from the factory. Refer to the Button map below for all panel navigation instructions
5 5. Page to the cmS list 6. Scroll to the Addr screen 7. Use the Up Arrow to select the desired address number. 8. Go to the home screen by