Aerco KC1000 Boiler equipped with Mod-Box Controller Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Équipement Aerco KC1000 Boiler equipped with Mod-Box Controller. AERCO KC1000 Boiler equipped with Mod-Box Controller User Manual [en] Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 82
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
Printed in U.S.A. REVISED 01/03/05
Instruction
No.
AERCO INTERNATIONAL, Inc., Northvale, New Jersey, 07647 USA
Installation, Operation
& Maintenance Instructions
KC Series
Gas Fired
Boiler System
Semi-Instantaneous, Condensing,
Forced Draft,
Natural Gas and Propane Fired,
Hot Water Boiler
1,000,000 BTU/HR Input
Applicable to Serial Numbers G-01-026 and above
Patent No. 4,852,524
GF-106
Vue de la page 0
1 2 3 4 5 6 ... 81 82

Résumé du contenu

Page 1 - Boiler System

Printed in U.S.A. REVISED 01/03/05 Instruction No. AERCO INTERNATIONAL, Inc., Northvale, New Jersey, 07647 U

Page 2 - Telephone Support

INSTALLATION 5 Figure 2.5b Pressure/Temperature Gauge Installation 2.3.5 CONDENSATE PIPING The KC Boiler is designed to condense and the installati

Page 3 - CONTENTS

INSTALLATION 6 To avoid damage to the unit, when pressure testing gas piping, isolate the unit from the supply gas piping. At no time should there be

Page 4

INSTALLATION 7 SSOVACTUATORBLOWERFRAMEELECTRICAL WIRING BOX Figure 2.8 AC Wiring Box Location NOTE: All electrical conduit and hardware should be

Page 5 - Foreword

INSTALLATION 8 2.6.1 CONSTANT SETPOINT MODE No external field wiring connections other than electrical supply connectins are required for this mode.

Page 6 - SAFETY PRECAUTIONS

INSTALLATION 9 2.9 FLUE GAS VENT INSTALLATION The AERCO Venting and Combustion Air Guide, GF-1050, must be consulted before any flue or inlet air v

Page 7

CONTROL PANEL OPERATING PROCEDURES10SECTION 3- CONTROL PANEL OPERATING PROCEDURESThe following is a guide to the operation of thecontrol panel. Initia

Page 8

CONTROL PANEL OPERATING PROCEDURES11The third LED, “ON”, indicates the status of thestart relay, (see Fig. 3.2). The start relay isinternal to the con

Page 9

CONTROL PANEL OPERATING PROCEDURES12To access the percent of firing rate press theINDEX button while in the primary menu until(Pct) is displayed in th

Page 10 - INSTALLATION

CONTROL PANEL OPERATING PROCEDURES13Figure 3.7Auto/Manual Display with Manual On3.4 THE SECONDARY MENUThe secondary menu is primarily related totempe

Page 11

CONTROL PANEL OPERATING PROCEDURES14# CYCLES =“DATE” “TIME”The number of timesthe controller hascompleted it’s startcycle, and the timeand dateSET DA

Page 12

Telephone Support Direct to AERCO Technical Support (8 to 5 pm EST, Monday through Friday) (800) 526-0288 AERCO

Page 13

CONTROL PANEL OPERATING PROCEDURES15 Figure 3.9Combustion Safeguard Status Indicator LEDLocation3.7 WATER LEVEL TEST and RESETSWITCHESThe water level

Page 14

CONTROL PANEL OPERATING PROCEDURES16CONNECTOR149VALVESHUT-OFFSAFETYSWITCHCLOSUREPROOF OF9A148145146147FROM Figure 3.11Proof of Closure Switch Locatio

Page 15 - WARNING:

CONTROL PANEL OPERATING PROCEDURES173.10 AFTER FLAMEOnce the control signal has gone below the stoplevel (see section 3.12 for Stop Levelexplanation)

Page 16

INITIAL START-UP18SECTION 4 - INITIAL START- UP4.1 INITIAL START- UP REQUIREMENTSThe initial start-up of the KC-1000 boiler iscomprised of the follow

Page 17

INITIAL START-UP191/4" NPT PLUG(INSTALLMANOMETERHERE)SSOVFigure 4.11/8” Gas Plug Location4.2.2 PREPARING THE FLUE VENTPROBE HOLE1. If the unit

Page 18 - 3.5.1 ANNUNCIATOR FUNCTION

INITIAL START-UP20 3. Using the 16” manometer installed as perSection 4.2.1, adjust the gas supplyregulator until a reading of 12” W.C. staticpressur

Page 19 - MESSAGE MEANING

INITIAL START-UP2116. Wait for the analyzer reading to settle, thencompare the new reading to Table 1. Repeatadjustment until oxygen is within thespe

Page 20

INITIAL START-UP22specified range. Firmly tighten the inlet airshutter locking nuts when finished. NOTE:Adjust the inlet air shutter only at 100%firin

Page 21 - CONNECTOR

INITIAL START-UP239. Remove the combustion analyzer probefrom the vent hole. Seal the probe hole andreplace the vent connection cover. 4.6 OVER TEMP

Page 22 - 3.12 START STOP LEVELS

MODE OF OPERATION 24SECTION 5- MODE OF OPERATION The following is a detailed description of the KC1000’s six modes of operation. Each unit is shippe

Page 23 - SECTION 4 - INITIAL START- UP

CONTENTSiGF-106 THE AERCO KC1000 GAS FIRED BOILEROperating & Maintenance InstructionsFOREWORDSection 1 SAFETY PRECAUTIONS-------------------------

Page 24

MODE OF OPERATION 255.2 CONSTANT SETPOINT MODE Constant setpoint mode of operation is when a non-changing, fixed, header temperature is desired. Co

Page 25

MODE OF OPERATION 265. Follow the above directions to change back to remote mode. NOTE: The unit automatically defaults to remote mode upon AC pow

Page 26

MODE OF OPERATION 27from an external source, the following functions must be correctly set. MENU FUNCTION SETTING Secondary Lore re Secondary FUNC

Page 27

MODE OF OPERATION 285.6.1 COMBINATION CONTROL SYSTEM FIELD WIRING Wiring for this system is between the BMS panel, the CCP and terminals 2 and 3 in

Page 28

SAFETY DEVICE TESTING 29SECTION 6-SAFETY DEVICE TESTING PROCEDURES 6.1 TESTING OF SAFETY DEVICES Periodic testing of all controls and safety devic

Page 29 - SECTION 5- MODE OF OPERATION

SAFETY DEVICE TESTING 30 8. Open the water shut-off valve in the return piping to the unit to fill the shell. 9. Open the water shut-off valve in t

Page 30

SAFETY DEVICE TESTING 31 1. Disconnect AC power from the unit. 2. Disconnect wire #17 from the air pressure switch located on the air/fuel valve (

Page 31

SAFETY DEVICE TESTING 32 10. Restore AC power to the unit. 11. Start the unit. WARNING! THIS IS A 120-VOLT AC COMBUSTION SAFEGUARD SYSTEM. POWER M

Page 32

MAINTENANCE 33SECTION 7 - MAINTENANCE 7.1 MAINTENANCE SCHEDULE The unit requires regular routine maintenance to keep up efficiency and reliability

Page 33

MAINTENANCE 34 Figure 7.1 Spark Ignitor and Flame Detector Location To inspect or replace the flame detector: 1. Put the green ON/OFF button on the

Page 34 - SAFETY DEVICE TESTING

CONTENTSiiSection 6 SAFETY DEVICETESTING PROCEDURES---------------------------296.1 Testing of Safety Devices6.2 Gas Pressure Fault Test6.3 Low Water

Page 35

MAINTENANCE 35 Figure 7.2 Grounding Terminal Location 7. Using a 7/16” socket or open end wrench remove the four 1/4”-20 nuts on the gas inlet pipe

Page 36

MAINTENANCE 36 Figure 7.6 Air/Fuel Valve Inlet Hose Clamp 16. Using an 11/16” wrench, loosen the compression fittings on the feedback tube between t

Page 37

MAINTENANCE 3726. Beginning with the manifold, reinstall all the components in the reverse order that they were removed. 7.6.1 PROPANE UNITS For

Page 38 - SECTION 7 - MAINTENANCE

TROUBLESHOOTING 38SECTION 8- TROUBLESHOOTING GUIDE This troubleshooting section is intended to serve as a guideline to determining and solving fault

Page 39

TROUBLESHOOTING 393. Replace the low gas pressure switch if it does not show continuity. 4. If there is no continuity, check for loose connectors

Page 40

TROUBLESHOOTING 408.2.1 EXHAUST TEMPERATURE SENSOR Start the unit and wait for the HI EXHAUST TEMP. message to display. 1. Using an accurate temp

Page 41

TROUBLESHOOTING 418.3.3 WATER LEVEL CIRCUIT 1. Remove AC power from the unit. 2. Open the control box to expose the wiring and internal componen

Page 42

TROUBLESHOOTING 429. Check the pins of the 15 pin connector for proper insertion or wear. 10. If the connectors, pins, and continuity are okay, re

Page 43 - TROUBLESHOOTING

TROUBLESHOOTING 437. If the flame fault still persists after checking the above, measure the flame detector lead voltage as per Section 8.5.7. 8.

Page 44

TROUBLESHOOTING 448.5.5 FLAME DETECTOR 1. Disconnect AC power to the unit. 2. Remove the flame detector as per Section 7.3. 3. Check the dete

Page 45

FOREWORDiiiForewordThe AERCO KC boiler is a true industry advance that meets the needs of today's energy andenvironmental concerns. Designed for

Page 46

TROUBLESHOOTING 45 29. Reconnect AC power to the unit and start the unit. 30. If the flame fault still persists, replace the combustion safeguard.

Page 47

TROUBLESHOOTING 464. If the blower starts but the Annunciator displays LOW AIR FLOW, proceed to Section 8.6.4. 5. If the unit has sealed combustio

Page 48

TROUBLESHOOTING 478.6.5 SOLID STATE RELAY 1. Referring to Appendix I,Item #17, open the control box and locate the solid state relay. 2. Locate

Page 49

TROUBLESHOOTING 484. Connect an ohmmeter across the blower proof switch and start the unit. 5. The blower proof switch should show continuity whil

Page 50

TROUBLESHOOTING 4914. If there is no continuity, replace the actuator or switch. 15. Start the unit. If the unit sequence resumes normal operation

Page 51

TROUBLESHOOTING 505. If the air/fuel valve does not rotate or is extremely difficult to rotate, replace the air/fuel valve. 6. Disconnect the 12 p

Page 52

APPENDIXAPPENDICESAPPENDIX ATemperature Controller MenusAPPENDIX BTemperature Controller Quick Programming GuideAPPENDIX CTemperature Sensor Resist

Page 53

APPENDIX A i PRIMARY MENU ITEM DESCRIPTIONS tout pct Setp Auto This is the actual outlet water temperature of

Page 54

APPENDIX A ii SECONDARY MENU ITEM DESCRIPTIONS CONSTANT SETPOINT FUNC OSAT Oat LLT Hlt Pb1 Int

Page 55

APPENDIX A iii Drt Addr LOre This is the derivative rate in % /.1°/sec. This adjusts response time to temperature changes at the o

Page 56 - APPENDICES

SAFETY PRECAUTIONS1SECTION 1 - SAFETY PRECAUTIONSInstalling or operating personnel MUST, atall times, observe all safety regulations. Thefollowing wa

Page 57 - APPENDIX A

APPENDIX A iv SECONDARY MENU ITEM DESCRIPTIONS INDOOR-OUTDOOR RESET MODE FUNC REFT RR OSAT Oat LLT

Page 58

APPENDIX A v Pb1 Int Drt Addr LOre This is the Proportional Band in 0F for the feedback of the controller. This

Page 59 - LOre

APPENDIX B viTEMPERATURE CONTROLLER QUICK REFERENCEPROGRAMMING GUIDEThe following is a “How To” guide that quickly shows how to access menu levels a

Page 60

APPENDIX B viiNOTE: The temperature controller defaults back to the PRIMARY menu from the SECONDARYmenu or the SECURE menu if there is no activity i

Page 61

APPENDIX B viii• SECURE MENU TO THE MAIN MENUWhile in the SECURE menu press INDEX and the ⇓ arrow key. This will place you in the SECONDARY menu. P

Page 63 - APPENDIX B

APPENDIX DxINDOOR\OUTDOOR RESET RATIO CHARTSHeader Temperature for a Building Reference Temperature of 50FRESET RATIOAirTemp0.6 0.8 1.0 1.2 1.4 1.6 1.

Page 64 - • CHANGING MENU ITEM VALUES

APPENDIX DxiRESET RATIOAirTemp0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.46565 65 65 65 65 65 65 65 65 656068 69 70 71 72 73 74 75 76 775571 73 75 77 79 81

Page 65 - APPENDIX C

APPENDIX DxiiHeader Temperature for a Building Reference Temperature of 75FRESET RATIOAirTemp0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.475F75 75 75 75 75

Page 66 - APPENDIX D

APPENDIX Dxiii Header Temperature for a Building Reference Temperature of 90FRESET RATIOAirTemp0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.490F90 90 90 90 9

Page 67

INSTALLATION 2 SECTION 2 - INSTALLATION PROCEDURES 2.1. RECEIVING THE UNIT Each KC unit is shipped as a single crated unit. The shipping weight

Page 68

APPENDIX ExivBOILER DEFAULT SETTINGS CONSTANT SET POINT MODEMENU LEVEL& CODEDESCRIPTION OF CODE FACTORYDEFAULTPRIMARY MENUtout OUTLET TEMPERATURE

Page 69

APPENDIX ExvBOILER DEFAULT SETTINGSINDOOR /OUTDOOR RESET MODEMENU LEVEL& CODEDESCRIPTION OF CODE DEFAULTVALUEPRIMARY MENUtout OUTLET TEMPERATURE A

Page 71

APPENDIX F xvii 1/4" CARBON STEEL SHELL, SA-53, GRADE BCU-NI HELICAL TUBE, SB-111, CDA-C706001/4" WALL CU-NI WELDED TUBE SB171, CDA-70635(8

Page 72 - APPENDIX F

APPENDIX F xviii

Page 73 - AP-A-568

APPENDIX F xix

Page 74

APPENDIX G xx

Page 75

APPENDIX G xxi

Page 76 - APPENDIX G

APPENDIX H xxii

Page 77

APPENDIX H xxiii

Page 78 - APPENDIX H

INSTALLATION 3 2.3 INSTALLATION The unit must be installed with the prescribed clearances for service as shown in Figure 2.1. The minimum clearance

Page 79

APPENDIX I xxiv 13 123446 FAN GUARD 12 123402 #6-32 X 3/8 LG PAN HEAD MACH. SCREW 11 123459 #6-32 X 2 LG PAN HEAD MACH. SCREW 10 123452 #8-

Page 80 - APPENDIX I

APPENDIX I xxv 18 123280-B_ TEMPERATURE CONTROLLER (NEED STYLE NUMBER ) 17 123803 SOLID STATE TIMER-ARTISAN CORP(123469 FOR SSAC INC.) 16 1

Page 81

HEAT EXCHANGERS • WATER HEATERS • BOILERSHEAT RECLAMATION SYSTEMS • CONTROL VALVES STEAM GENERATORSHOT WATER SYSTEMSAERCO INTERNATIONAL, INC. • 159 P

Page 82

INSTALLATION 4 Whether installing single or multiple units, install the piping and accessories as shown in the appropriate piping diagram located in

Commentaires sur ces manuels

Pas de commentaire