Aerco BMS 168 Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Équipement Aerco BMS 168. AERCO BMS 168 User Manual [en] Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 86
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
Boiler Management
System
Installation
Instructions
AERCO International, Inc.
159 Paris Avenue
Northvale, NJ 07647-0128
REVISED 3/13/08
Boiler Management
System
Operation &
Troubleshooting
DISPLAY MODE
HDR
TEMP
Display Header
Temp.,
o
F
Hold Key for
Header Set
Raise/Lower
To Change
DISPLAY
ADJ
HEADER SET INDOOR AIR
AIR
TEMP
Display Outside Air
Temp.,
o
F
%
LOAD
Display % Load &
No. of Units Operating
Display/Change Indoor
Sensor Reference Temp.,
o
F
OFF
SET
SET
POINT
PROP
BAND
CONFG
SYS
%
LOAD
HDR
TEMP
LIMIT
FIELD
ADJ
HDR
TEMP
AIR
TEMP
REF
TEMP
OFF
SET
ON OFF
CONFIG
SYS
AERCO INTERNATIONAL INC., NORTHVALE, N.J.
RESET
RATIO
PROP
BAND
SET
POINT
SYS
START
LEVEL
Display/Change Setpoint
Temp when Activated
Display/Change
Hdr. Temp. / Indoor Ref. Temp.
System
Configuration
FOR USE W/ INDOOR TEMP. SENS.
FIELD ADJUSTMENT MODE
FIELD
ADJ
L.E.D. "On"
Enables Field Adjustment
SYS
START
TEMP
Select System Start Option
Display/Change Outside Air
Temp. for System Start
REF
TEMP
Display/Change
Bldg Ref Temp — Indoor/Outdoor
Reset Mode
Hdr Set Temp Constant Set
Point Mode
HDR
TEMP
LIMIT
RESET
RATIO
%
LOAD
OFF
SET
Display/Change
Minimum Or Maximum
Header Temp.
Display/Change
Header Temp. / Outside Air Temp.
(Alarm Cancel) Reset Alarm Contact
Set Date
And Time
Set Up
Set Back
Clock
CONFG
SYS
OFF
Select Fault
Alarm Relay
Options
ON
Enable BMS
Disable BMS
AERCO International, Inc.
159 Paris Avenue
Northvale, NJ 07647-0128
GF-108M
Applicable to Serial Numbers 329985 and above
(EPROM Rev. K and above)
Vue de la page 0
1 2 3 4 5 6 ... 85 86

Résumé du contenu

Page 1 - Boiler Management

Boiler Management SystemInstallationInstructionsAERCO International, Inc.159 Paris Avenue Northvale, NJ 07647-0128

Page 2 - Telephone Support

Time Delay Between Boiler Starts: A fixed, 30-second time delay between boiler starts ensures smooth energy input without spikes in electrical, gas,

Page 3 - SYSTEM (BMS) 1-1

Section 3 ______________________________ Installing the BMS________ Please follow the installation procedure in the order presented. Incorrect wi

Page 4 - (Continued)

WARNING! Turn off AC input power to the BMS to avoid electrical shock. 3.3 PULSE WIDTH MODULATION WIRING Pulse width modulation (PWM) wiring conn

Page 5

Connect the RS485 wiring at the BMS as follows: • Connect the positive (+) lead to the +(B) terminal of JP11. • Connect the negative (-) lead to th

Page 6 - List of Figures

3.6 INTERLOCK WIRING The BMS is equipped with two interlocks designated Interlock 1 (INT 1) and Interlock 2 (INT 2). Since both interlocks must be c

Page 8

Figure 2 BMS MOUNTING 3-6

Page 9 - Features of

Figure 3 RECOMMENDED WIRE ROUTING LOCATIONS AT THE BMS 3-7

Page 10 - (Enable/Disable Contacts)

Figure 4 PWM COMMUNICATION OUTPUTS AT THE BMS 3-8

Page 11 - BMS________

Figure 5 PULSE WIDTH MODULATION CONNECTIONS AT KC SERIES BOILER WITH MODULAR CONTROL BOX 3-9

Page 12 - 3.4 RS485 (MODBUS) WIRING

Telephone Support Direct to AERCO Technical Support (8 to 5 pm EST, Monday through Friday): 1-800-526-0288 AERCO

Page 13 - 3.5 SENSOR INSTALLATION

mA OUTRS-485 COMM.+-+-ANALOG INSENSOR COMMONOUTDOOR SENSOR INREMOTE INTL'K INB.M.S. (PWM) INSHIELD+-+-AUX SENSOR INNOT USEDEXHAUST SWITCH

Page 14 - 3.8 SET BACK

Figure 7 PWM CONNECTIONS AT BENCHMARK BOILER WITH MODULAR CONTROL BOX 3-11

Page 15

mA OUTRS-485 COMM.+-+-ANALOG INSENSOR COMMONOUTDOOR SENSOR INREMOTE INTL'K INB.M.S. (PWM) INSHIELD+-+-AUX SENSOR INNOT USEDEXHAUST SWITCH

Page 16 - BMS MOUNTING

Figure 9 BMS RS485 & RS232 CONNECTOR LOCATIONS 3-13

Page 17 - Figure 3

Figure 10 BMS RS485 & RS232 CONNECTOR PIN ASSIGNMENTS 3-14

Page 18 - Figure 4

1/2 “ NPT Figure 11 HEADER SENSOR INSTALLATION WITH WELL 3-15

Page 19 - Figure 5

3-16 Figure 12 OUTSIDE AIR SENSOR MOUNTING AND CONNECTIONS

Page 20 - Figure 6

Section 4 ______________________________ Familiarizing Yourself With the BMS_____ 4.1 ABOUT BMS MODES The BMS has three basic modes: Normal Mod

Page 21 - PWM CONNECTIONS AT

4-2 Figure 13 NORMAL & FIELD ADJUST MODE OVERLAY

Page 22 - Figure 8

4-3 Figure 14 SYSTEM CONFIGURATION MODE OVERLAY

Page 23 - Figure 9

Table of Contents Page SECTION 1 ABOUT YOUR NEW BOILER MANAGEMENT SYSTEM (BMS) 1-1 SECTION 2 FEATURES OF THE BMS

Page 24

NOTE Sample Normal Mode displays with their Factory Default values are provided in Appendix C. 4.2 NORMAL MODE DISPLAYS AND FUNCTIONS When power is

Page 25 - Figure 11

4.2.12 ▲ and ▼ Arrow Keys The ▲ and ▼ arrow keys are not active in this mode, since no changes can be made to the displayed settings 4.2.13 ON a

Page 26 - Figure 12

7. Repeatedly pressing the HDR TEMP key allows the NETW BOILER ADDRESS to be set for each boiler being controlled on the Modbus Net-work. 4.3.2 AIR

Page 27 - Yourself With

4.3.5 SYS START TEMP When in the Field Adjust Mode, the SYS START TEMP key has two functions. First, It lets you select the outdoor temperature at w

Page 28 - Figure 13

4.3.8 FIELD ADJ The FIELD ADJ key LED should be lit to indicate that the BMS is already in the Field Adjust Mode. Pressing and releasing this key wh

Page 29 - Figure 14

5. Press key a fifth time. OFFSET OFF TIME DAY 1 Æ 0: 0 is displayed prompting Hours to be entered for off time. Since the BMS uses a 24-hour clock

Page 30 - AND FUNCTIONS

Selecting INTERLOCK 2 causes the Fault Relay to close and generate an alarm only when Interlock 2 opens. However, if INTERLOCK 1 opens, a fault mes

Page 31 - DISPLAYS AND FUNCTIONS

If SWITCH INPUTS is selected, the BMS will automatically switch to Constant Setpoint mode if a sensor or remote input error occurs. Once the sensor

Page 32

4.4.4 START LEVEL and STOP LEVEL Keys These keys allow you to set the energy levels (firing rate percentages) at which additional boilers are staged

Page 33 - 4.3.7 HDR TEMP LIMIT

As the load drops off, the firing rates decrease. When all boilers reach the stop level, the first boiler turned on will be shut off by the BMS and i

Page 34 - 4.3.11 OFFSET

Table of Contents (Continued) 4.2.13 ON and OFF Keys 4-5 4.2.14 CONFIG SYS 4-5 4.3 FIELD ADJUST MODE FUNCTIONS 4-5 4.3.1 HDR TE

Page 35 - Using the OFFSET key:

specific installation. The factory defaults preset by AERCO work well for most applications. In instances when there is a large error between the set

Page 36 - FUNCTIONS

4.4.8 AUX RELAY This key is used to display or change the firing rate at which the Auxiliary Relay opens and closes. The Auxiliary Relay is typically

Page 38 - 4.4.5 BLR OP MODE

Section 5 ______________________________ Programming the BMS Mode of Operation__ Prior to programming, the BMS must be mounted and all required w

Page 39

5.1.4 Entering the Building Reference Temperature To enter the Building Reference Temperature, perform the following steps: 1. Enter Field Adjust

Page 40 - 78% firing

NOTE Steps 5, 6 and 7 scale the 20 mA Remote Signal to the selected HDR HIGH LIMIT and HDR LOW LIMIT settings. 5. Select the desired header high temp

Page 41 - , or when the BMS

5.4.1 C-More Control System PWM Setup For PWM communication, each boiler’s C-More Control System must have the Configuration Menu items properly set

Page 42

5.6 TESTING THE SYSTEM The following procedure places a load on the system and will begin firing the boilers. At this point it is very important to m

Page 44 - SETPOINT MODE

Appendix A ____________________________ SPECIFICATIONS INPUTS POWER Input voltage 120 VAC, 60Hz, 1 phase, ± 10%, fused at 1 A OUTSIDE AIR SEN

Page 45 - ODULATION (PWM)

Table of Contents (Continued) SECTION 5 PROGRAMMING THE BMS MODE OF OPERATION 5.1 INDOOR/OUTDOOR RESET MODE 5-1 5.1.1 Selecting Indoor/Outdoor R

Page 46 - AND POLLING

A-2 Appendix A (cont.) ________________________ CURRENT LOOP Input resistance 250 Ohms Protection Isolated from AC line potential, fuse-protect

Page 47 - 5.6 TESTING THE SYSTEM

A-3 Appendix A (cont.) ________________________ BOILER DRIVE Drive Type (PWM) Signal (with 12 msec time base) Optically-isolated, pulse width

Page 48

A-4 Appendix A (cont.) ________________________ DEFAULT VALUES System State Halted (stop mode) Header Set Mode Indoor/Outdoor Reset Indoor Air

Page 49 - ____________________________

B-1 Appendix B _____________________________ Methods for Determining Reset Schedule and Indoor/Outdoor Reset Ratio Charts Using the Charts to Dete

Page 50 - ________________________

B-2 Appendix B (cont.) _________________________ Header Temperature for a Building Reference Temperature of 50°F Reset Ratio Air Temp (°F)

Page 51

B-3 Appendix B (cont.) _________________________ Header Temperature for a Building Reference Temperature of 65°F Reset Ratio Air Temp (0F)

Page 52

B-4 Appendix B (cont.) __________________________ Header Temperature for a Building Reference Temperature of 70°F Reset Ratio Air Temp (0F) 0.

Page 53 - - RR (TR-TO)+TR, where:

B-5 Appendix B (cont.) __________________________ Header Temperature for a Building Reference Temperature of 75°F Reset Ratio Air Temp (°F) 0

Page 54 - Temperature of 50°F

B-6 Appendix B (cont.) _________________________ Header Temperature for a Building Reference Temperature of 80°F Reset Ratio Air Temp (°F) 0.

Page 55 - Temperature of 65°F

B-7 Appendix B (cont.) _________________________ Header Temperature for a Building Reference Temperature of 90°F Reset Ratio Air Temp (°F) 0.6

Page 56 - Temperature of 70°F

iv List of Figures Figure 1 Typical BMS Installation 3-5 Figure 2 BMS Mounting 3-6 Figure 3 Wire Routing Locations at the BMS 3-7

Page 58 - Temperature of 80°F

C-1 Appendix C _____________________________ Normal (Read-Only) Mode Display Messages and Defaults Key Display Message Default Range HDR TEMP HEA

Page 60

D-1 Appendix D _____________________________ Field Adjust Mode Display Messages and Defaults Key Display Message Default Range HDR TEMP (Press Onc

Page 61

D-2 Appendix D (cont.)__________________________ Field Adjust Mode Display Messages and Defaults (cont.) Key Display Message Default Range SYS ST

Page 62

E-1 Appendix E _____________________________ Config Sys Mode Display Messages and Defaults Key Display Message Defaults Range TEMP FAIL MODE TEM

Page 64 - __________________________

F-1 Appendix F _____________________________ Temperature Sensor Resistance Data Temperature (°F) Resistance (ohms) Temperature (°F) Resistance

Page 66

G-1 Appendix G _____________________________ Parts List Part Number Description Comment GP-122783 Boiler Management System (BMS) Complete BM

Page 67

Section 1 ______________________________ About Your New Boiler Management System (BMS) AERCO’s Boiler Management System (BMS), stages and modulat

Page 69 - Parts List

H-1 Appendix H _____________________________ TROUBLESHOOTING When a fault occurs in the boiler plant, the BMS flashes error messages at 2-second

Page 70

H-2 Appendix H _____________________________ Table H1 Error Messages - Continued Fault Message Description & Possible cause SYSTEM ERROR,

Page 71

H-3 Appendix H ____________________________ Table H2 Common Problems Problem Possible Causes Solution Boiler plant not started by BMS • Outsi

Page 72

H-4 Appendix H _____________________________ Table H2 Common Problems - Continued Problem Possible Causes Solution Boilers overshooting setpoi

Page 73

I-1 Appendix I _____________________________ GENERAL WIRING

Page 75

Appendix J _____________________________ PROGRAMMING THE BMS USING RS-232 COMMUNICATION Introduction The RS-232 port on the left side of the BMS

Page 76

Appendix J (cont.) __________________________ Programming Procedure BMS functions which can be viewed or changed are listed in Table J-1 along

Page 77

Appendix J (cont.) __________________________ Table J-1. BMS COMMANDS No. COMMAND ENTRY RANGE FACTORY DEFAULT 00 Header Temperature (°

Page 79

Appendix J (cont.) __________________________ Table J-1. BMS COMMANDS No. COMMAND ENTRY RANGE FACTORY DEFAULT 21 Aux Relay Mode 0 =

Page 80

J-5 Appendix J (cont.) __________________________ Table J-1. BMS COMMANDS – (Continued) No. COMMAND ENTRY RANGE FACTORY DEFAULT 45 (Day

Page 81

Appendix J (cont.) __________________________ Table J-1. BMS COMMANDS – (Continued) No. COMMAND ENTRY RANGE FACTORY DEFAULT 87 RS232 M

Page 82

Appendix J (cont.) __________________________ Table J-1. BMS COMMANDS – (Continued) No. COMMAND ENTRY RANGE FACTORY DEFAULT 101 Net Bo

Page 83

Appendix J (cont.) __________________________ Table J-1. BMS COMMANDS – (Continued) No. COMMAND ENTRY RANGE FACTORY DEFAULT 113 Net Bo

Page 84

J-9 Appendix J (cont.) __________________________ Table J-1. BMS COMMANDS – (Continued) No. COMMAND ENTRY RANGE FACTORY DEFAULT 124

Page 86

Section 2 ______________________________ Features of the BMS____ APPLICATION FLEXIBILITY Three different system or control options can be select

Commentaires sur ces manuels

Pas de commentaire