Hoffman Specialty
Installation & Maintenance
Instructions
HS-222(E)
Float and Thermostatic Traps
Series H, C and X
Before using product, read and understand instructions.
Save these instructions for future reference.
All work must be performed by qualified personnel trained in the proper application,
installation, and maintenance of steam systems in accordance with all applicable codes
and ordinances.
To prevent serious burns, wear heat resistant gloves when opening and closing steam
valves, or handling hot equipment.
To prevent serious burns, the internal pressure of the trap must be 0 psi (0 bar) before
servicing.
To prevent serious personal injury from steam pipe blow down, connect a temporary
pipe between the steam pipe opening and a drain, or stand at least 100 ft. (30 m) from
the front of the pipe opening.
To prevent property damage, personal injury, or death, cap off the gate valves if they are
not connected to a drain and when they are not in use for test or pressure relief.
Failure to follow this warning could cause property damage, personal injury or death.
!
WARNING
CAUTION
WARNING
®
Series C
1
1
4 & 1
1
2 NPT
Series C
2 NPT
Series X
2 NPT
Series C
2
1
2 NPT
Series H
Ratings
Maximum Max. Operating
NPT Size - in. Temperature Pressure
°F (°C) psig (bar)
3
4
”, 1” and
1
1
4
” H
406 (208)
175 (12.1)
1
1
4
” C and All
1
1
2
” -
2
1
2
377 (192)
Vue de la page 0
1 2 3 4 5 6

Résumé du contenu

Page 1 - Series H, C and X

Hoffman SpecialtyInstallation & Maintenance Instructions HS-222(E)Float and Thermostatic TrapsSeries H, C and X• Before using product, read and un

Page 2 - INSTALLATION –

INLETTESTINLETOUTLETOUTLETTESTOUTLETINLETTESTINLETOUTLETTESTT21. Determine where to install the trap, based on the following requirements:• The trap m

Page 3 - TYPICAL PIPING DIAGRAMS

Shut-OffValve"Y" StrainerTo DrainTo Return LineTrapGravity Return toVented ReceiverTest ValveEquipment Drain PointStaticHeadDirt PocketInle

Page 4 - (0 bar) before servicing

4REPAIR PROCEDURES FOR ALL TRAPSREMOVAL FROM SERVICE1. Close inlet and outlet supply valves and allow unit tocool. If a test valve is installed, open

Page 5 - " Units

5RETURN TO SERVICE10. Insert and securely tighten drain plug.11. Open supply valve on trap outlet side, slowly open thesupply valve to the trap inlet.

Page 6 - Hoffman Specialty

TROUBLESHOOTINGProblem:1. Improper heating.a. Cause: Thermostat failed closed and prevents air from escaping.Test: Blow air through the thermostatwhen